Differential pressure measurement
Polyurethane (polyether) diaphragm and brass 1/4” NPT
(female) pressure connection
Adjustable Range: 4...45 psid / 0,3...3,1 bar
Typical Deadband: 1 psid / 68,9 mbar
Max. Working Pressure: 0...150 psi / 0...10,3 bar
Proof Pressure: 150 psi / 10,3 bar
Ambient Temperature: 30° to 160°F (-1° to 71°C). Set point
typically shifts less than ±0.6% of range for a
50°F (28°C) ambient temperature change
Max. Media Temperature: 200°F (93°C) at 100 psi working
pressure
Enclosure: Complies with enclosure type 4 requirements for
indoor installation with optional
water tight conduit connector. Reinforced polyester body,
stainless steel cover with
gasket.
Switch Output: One SPDT snap-action switch; switch may be
wired "normally open" or "normally
closed".
Electrical Connection: 7/8" hole for optional 1/2" NPT conduit
connector. Terminal block with screw
terminals. Max wire size 16 AWG
Gefahrgut für Luft- oder Seefracht: nein
Wir informieren Sie gern darüber, falls der Preis dieses Artikels Ihrem Wunschpreis entspricht.